Fire Protection System Attachments

Components for rigid earthquake brace assemblies that are UL Listed and/or FM Approved for Fire Protection Installations.

Pages: 1 2 3

Sway Brace Attachment
-Enlarge Picture- enlarge


    Underwriters Laboratories cul listed
  1.   Information  
  2.   Resources  
  3.   Pricing  

Information

Fig. 2002
Sway Brace Attachment

  • For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: The Fig. 2002 is used in conjunction with TOLCO 900 Series sway brace attachments and joined together with bracing pipe.
  • UL Listed in the USA and Canada
  • For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
  • Size Range - Pipe size to be braced: 2 1/2" - 8" all steel schedules.

This product meets the following approvals:
    Underwriters Laboratories cul listed

Download Printable Cut Sheet

Submittals for Fig. 2002 - Sway Brace Attachment

Download Printable Cut Sheet.

Fig. 2002 - Sway Brace Attachment

Size Range - Pipe size to be braced: 2 1/2" thru 8" all steel schedules. Consult factory when bracing other than steel. The Fig. 2002 accepts brace pipes sizes 1 1/2" and 2" steel schedule 100 through schedule 40.
Material - Carbon Steel
Function - For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: The Fig. 2002 is used in conjunction with a TOLCO 900 Series sway brace attachments and joined together with bracing pipe. Install per NFPA 13 and/or TOLCO State of California OSHPD Approved Seismic Restrain Manual.
Features - Unique design will not damage thin wall, plastic, copper or ductile iron pipe. Easy verification of proper installation by tightening bolts until ears touch.
Installation - Place Fig. 2002 over pipe to be braced. Slide bracing pipe through attachment and tighten hex nuts until ears touch.
Approvals - Underwriter's Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
Finish - Plain
Note - Available in Electro-Galvanized and HDG finish. Order By - Figure number, pipe size to be braced, pipe size used for bracing (1 1/2" or 2") and finish.
Important Note - The Fig. 2002 is precision manufactured to perform its function as a critical component of a complete bracing assembly. To ensure performance, the UL Listing requires that the Fig. 2002 must be used only with other TOLCO bracing products.
Component of State of California OSHPD Approved Seismic Restraints System


Pricing

Receive a quote for Fig. 2002 - Sway Brace Attachment

Download pricing catalog




Sway Brace Attachment
-Enlarge Picture- enlarge


FM APPROVED     Underwriters Laboratories cul listed
  1.   Information  
  2.   Resources  
  3.   Pricing  

Information

Fig. 1001
Sway Brace Attachment

  • For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: The Fig. 1001 is used in conjunction with a TOLCO 900 Series fitting and joined together with bracing pipe per NFPA 13, forming a complete sway brace assembly.
  • UL Listed in the USA and Canada
  • Approved by the State of California Office of Statewide Health Planning and Development (OSHPD)
  • For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
  • Size Range - Pipe size to be braced: 2 1/2" - 8" IPS. Pipe size used for bracing:1" and 1 1/4" Schedule 40 IPS.

This product meets the following approvals:
FM APPROVED     Underwriters Laboratories cul listed

Download Printable Cut Sheet

Submittals for Fig. 1001 - Sway Brace Attachment

Download Printable Cut Sheet.

Fig. 1001 - Sway Brace Attachment

Size Range - Pipe size to be braced: 2 1/2" thru 8" IPS.* Pipe size used for bracing: 1" and 1 1/4" Schedule 40 IPS.
Material - Carbon Steel
Function - For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: The Fig. 1001 is used in conjunction with a TOLCO 900 Series fitting and joined together with bracing pipe per NFPA 13, forming a complete sway brace assembly.
Features - Can be used to brace schedules 7 through 40 IPS. Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of bracing pipe. Can be used as a component of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below.
Installation Note - Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set bolts until heads bottom out. A minimum of 1" pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced.
Approvals - Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
Finish - Plain
Note - Available in Electro-Galvanized and HDG finish.
Order By - Indicate pipe size to be braced followed by pipe size used for bracing, figure number and finish.
Important Note - The Fig. 1001 is precision manufactured to perform its function as a critical component of a complete bracing assembly. To ensure performance, the UL Listing requires that the Fig. 1001 must be used only with other TOLCO bracing products. The Fig 1001 is not intended for use with the Fig. 907 4-Way Longitudinal Brace Attachment.
Component of State of California OSHPD Approved Seismic Restraints System Maximum Design Load
Sch. 7 - 1600 lbs.
Sch. 10 & 40 w/1" Brace Pipe - 2015 lbs.
Sch. 10 & 40 w/11/4" Brace Pipe - 2765 lbs.

FM Approved Design Loads*
2½ " - 2400 lbs.
3" - 4" - 2500 lbs.
5" - 8" - 1500 lbs.


Pricing

Receive a quote for Fig. 1001 - Sway Brace Attachment

Download pricing catalog




"Fast Clamp" Sway Brace Attachment
-Enlarge Picture- enlarge


FM APPROVED     Underwriters Laboratories cul listed
  1.   Information  
  2.   Resources  
  3.   Pricing  

Information

Fig. 1000
"Fast Clamp" Sway Brace Attachment

  • For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: Fig. 1000 is used in conjunction with a TOLCO Fig. 900 Series Fitting and joined together with bracing pipe per NFPA 13* or TOLCO OSHPD Approved Seismic Manual, forming a complete sway brace assembly.
  • UL Listed in the USA and Canada
  • Approved by the State of California Office of Statewide Health Planning and Development (OSHPD)
  • For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
  • Size Range - Pipe size to be braced: 1" - 6" Schedule 10 - 40. Pipe size used for bracing:1" and 1 1/4" Schedule 40 IPS.

This product meets the following approvals:
FM APPROVED     Underwriters Laboratories cul listed

Download Printable Cut Sheet

Submittals for Fig. 1000 - "Fast Clamp" Sway Brace Attachment

Download Printable Cut Sheet.


Pricing

Receive a quote for Fig. 1000 - "Fast Clamp" Sway Brace Attachment

Download pricing catalog




Universal Swivel Sway Brace Attachment
-Enlarge Picture- enlarge


FM APPROVED     Underwriters Laboratories cul listed
  1.   Information  
  2.   Resources  
  3.   Pricing  

Information

Fig. 980
Universal Swivel Sway Brace Attachment

  • Multi-functional attachment to structure or braced pipe fitting.
  • UL Listed in the USA and Canada
  • Approved by the State of California Office of Statewide Health Planning and Development (OSHPD)
  • For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
  • Size Range - One size fits bracing pipe 1" - 2", TOLCO 12 gauge channel, and all structural steel up to 1/4" thick.

This product meets the following approvals:
FM APPROVED     Underwriters Laboratories cul listed

Download Printable Cut Sheet

Submittals for Fig. 980 - Universal Swivel Sway Brace Attachment

Download Printable Cut Sheet.


Pricing

Receive a quote for Fig. 980 - Universal Swivel Sway Brace Attachment

Download pricing catalog




Straight Sway Brace Fitting
-Enlarge Picture- enlarge


    Underwriters Laboratories cul listed
  1.   Information  
  2.   Resources  
  3.   Pricing  

Information

Fig. 975
Straight Sway Brace Fitting

  • For bracing pipe against sway and seismic disturbance. The building attachment component of a sway brace system: Fig. 975 is used in conjunction with the Fig. 1000, Fig. 1001 or with a Fig. 4A Pipe Clamp and joined together with a brace pipe per NFPA 13.
  • UL Listed in the USA and Canada
  • Size Range - Pipe size to be braced: 1"

This product meets the following approvals:
    Underwriters Laboratories cul listed

Download Printable Cut Sheet

Submittals for Fig. 975 - Straight Sway Brace Fitting

Download Printable Cut Sheet.


Pricing

Receive a quote for Fig. 975 - Straight Sway Brace Fitting

Download pricing catalog


Pages: 1 2 3


 

2D/3D CAD Drawings

in the news

DID YOU KNOW?

TOLCO’s new Fig. 828 is an easy way to attach a sway brace to structural steel.






print this page